Effect of Synchronous Generator Loading on Automatic Voltage Regulation
No Thumbnail Available
File version
Author(s)
Pota, Hemanshu R.
Tilwalli, Prahlad
Hossain, Jahangir
Tilwalli, Prahlad
Hossain, Jahangir
Griffith University Author(s)
Primary Supervisor
Other Supervisors
Editor(s)
IEEE PES Committee
Date
2013
Size
File type(s)
Location
Vancouver, Canada
License
Abstract
This paper presents two basic results with proof. One result backs up the industry practice of using the first-order synchronous machine model for automatic voltage regulator (AVR) tuning. The other result gives a condition on when the loading of the generator results in an unstable system with the AVR tuned for the first-order model. This analysis also implies that when generator loading destabilises the system the standard IEEE AVR models are inadequate to guarantee stability for the loaded generator.
Journal Title
Conference Title
IEEE Power and Energy Society General Meeting
Book Title
Edition
Volume
Issue
Thesis Type
Degree Program
School
Publisher link
DOI
Patent number
Funder(s)
Grant identifier(s)
Rights Statement
Rights Statement
Item Access Status
Note
Access the data
Related item(s)
Subject
Power and Energy Systems Engineering (excl. Renewable Power)