Effect of Synchronous Generator Loading on Automatic Voltage Regulation

No Thumbnail Available
File version
Author(s)
Pota, Hemanshu R.
Tilwalli, Prahlad
Hossain, Jahangir
Griffith University Author(s)
Primary Supervisor
Other Supervisors
Editor(s)

IEEE PES Committee

Date
2013
Size
File type(s)
Location

Vancouver, Canada

License
Abstract

This paper presents two basic results with proof. One result backs up the industry practice of using the first-order synchronous machine model for automatic voltage regulator (AVR) tuning. The other result gives a condition on when the loading of the generator results in an unstable system with the AVR tuned for the first-order model. This analysis also implies that when generator loading destabilises the system the standard IEEE AVR models are inadequate to guarantee stability for the loaded generator.